CVE-2022-2081
Severity CVSS v4.0:
Pending analysis
Type:
CWE-787
Out-of-bounds Write
Publication date:
04/01/2024
Last modified:
25/09/2024
Description
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function.
Impact
Base Score 3.x
7.50
Severity 3.x
HIGH
Vulnerable products and versions
| CPE | From | Up to |
|---|---|---|
| cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:* | 12.0.1 (including) | 12.0.13 (including) |
| cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:* | 12.2.1 (including) | 12.2.11 (including) |
| cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:* | 12.4.1 (including) | 12.4.11 (including) |
| cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:* | 12.6.1 (including) | 12.6.7 (including) |
| cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:* | 12.7.1 (including) | 12.7.3 (including) |
| cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:* | 13.2.1 (including) | 13.2.4 (including) |
| cpe:2.3:o:hitachienergy:rtu520_firmware:13.3.1:*:*:*:*:*:*:* | ||
| cpe:2.3:h:hitachienergy:rtu520:-:*:*:*:*:*:*:* | ||
| cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:* | 12.0.1 (including) | 12.0.13 (including) |
| cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:* | 12.2.1 (including) | 12.2.11 (including) |
| cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:* | 12.4.1 (including) | 12.4.11 (including) |
| cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:* | 12.6.1 (including) | 12.6.7 (including) |
| cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:* | 12.7.1 (including) | 12.7.3 (including) |
| cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:* | 13.2.1 (including) | 13.2.4 (including) |
| cpe:2.3:o:hitachienergy:rtu530_firmware:13.3.1:*:*:*:*:*:*:* |
To consult the complete list of CPE names with products and versions, see this page