CVE-2017-6868
Severity CVSS v4.0:
Pending analysis
Type:
CWE-287
Authentication Issues
Publication date:
07/07/2017
Last modified:
20/04/2025
Description
An Improper Authentication issue was discovered in Siemens SIMATIC CP 44x-1 RNA, all versions prior to 1.4.1. An unauthenticated remote attacker may be able to perform administrative actions on the Communication Process (CP) of the RNA series module, if network access to Port 102/TCP is available and the configuration file for the CP is stored on the RNA's CPU.
Impact
Base Score 3.x
8.10
Severity 3.x
HIGH
Base Score 2.0
6.80
Severity 2.0
MEDIUM
Vulnerable products and versions
CPE | From | Up to |
---|---|---|
cpe:2.3:a:siemens:simatic_cp_44x-1_redundant_network_access_modules:*:*:*:*:*:*:*:* | 1.4.0 (including) |
To consult the complete list of CPE names with products and versions, see this page
References to Advisories, Solutions, and Tools
- http://www.securityfocus.com/bid/99234
- http://www.securitytracker.com/id/1038788
- https://ics-cert.us-cert.gov/advisories/ICSA-17-173-01
- https://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-126840.pdf
- http://www.securityfocus.com/bid/99234
- http://www.securitytracker.com/id/1038788
- https://ics-cert.us-cert.gov/advisories/ICSA-17-173-01
- https://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-126840.pdf