Description
In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states.
Impact
Base Score 3.x
6.70
Severity 3.x
MEDIUM
Base Score 2.0
7.20
Severity 2.0
HIGH
Vulnerable products and versions
| CPE | From | Up to |
|---|---|---|
| cpe:2.3:o:schneider-electric:triconex_tricon_mp_3008_firmware:*:*:*:*:*:*:*:* | 10.0 (including) | 10.0-10.4 (including) |
| cpe:2.3:h:schneider-electric:triconex_tricon_mp_3008:-:*:*:*:*:*:*:* |
To consult the complete list of CPE names with products and versions, see this page