CVE-2019-13553
Severity CVSS v4.0:
Pending analysis
Type:
CWE-798
Use of Hard-coded Credentials
Publication date:
25/10/2019
Last modified:
10/02/2020
Description
Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems is configured using hard-coded credentials. These credentials could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point.
Impact
Base Score 3.x
9.80
Severity 3.x
CRITICAL
Base Score 2.0
10.00
Severity 2.0
HIGH
Vulnerable products and versions
CPE | From | Up to |
---|---|---|
cpe:2.3:o:carel:pcoweb_firmware:*:*:*:*:*:*:*:* | a1.5.3 (including) | b1.2.4 (including) |
cpe:2.3:h:rittal:chiller_sk_3232:-:*:*:*:*:*:*:* |