CVE-2020-24685
Severity CVSS v4.0:
Pending analysis
Type:
Unavailable / Other
Publication date:
09/02/2021
Last modified:
16/02/2021
Description
An unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC. After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application. This issue affects: ABB AC500 V2 products with onboard Ethernet version 2.8.4 and prior versions.
Impact
Base Score 3.x
8.60
Severity 3.x
HIGH
Base Score 2.0
5.00
Severity 2.0
MEDIUM
Vulnerable products and versions
| CPE | From | Up to |
|---|---|---|
| cpe:2.3:o:abb:ac500_cpu_firmware:*:*:*:*:*:*:*:* | 2.8.5 (excluding) | |
| cpe:2.3:h:abb:pm573-eth:2.0:*:*:*:*:*:*:* | ||
| cpe:2.3:h:abb:pm583-eth:2.0:*:*:*:*:*:*:* |
To consult the complete list of CPE names with products and versions, see this page