CVE-2022-30314
Severity CVSS v4.0:
Pending analysis
Type:
CWE-798
Use of Hard-coded Credentials
Publication date:
28/07/2022
Last modified:
13/02/2024
Description
Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).
Impact
Base Score 3.x
4.60
Severity 3.x
MEDIUM
Vulnerable products and versions
| CPE | From | Up to |
|---|---|---|
| cpe:2.3:o:honeywell:safety_manager_firmware:*:*:*:*:*:*:*:* | r160.1 (excluding) | |
| cpe:2.3:h:honeywell:safety_manager:-:*:*:*:*:*:*:* |
To consult the complete list of CPE names with products and versions, see this page