CVE-2024-1573
Severity CVSS v4.0:
Pending analysis
Type:
CWE-306
Missing Authentication for Critical Function
Publication date:
04/07/2024
Last modified:
08/01/2026
Description
Missing Authentication for Critical Function vulnerability in the mobile monitoring feature of Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97 to 10.97.2, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.2, and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting.<br />
* “Automatic log in” option is enabled in the security setting.<br />
* The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account.<br />
* The IcoAnyGlass IIS Application Pool account is included in GENESIS64 and MC Works64 Security and has permission to log in.
Impact
Base Score 3.x
5.90
Severity 3.x
MEDIUM
References to Advisories, Solutions, and Tools
- https://jvn.jp/vu/JVNVU98894016/
- https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03
- https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf
- https://jvn.jp/vu/JVNVU98894016/
- https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03
- https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf