CVE-2017-7575
Severity CVSS v4.0:
Pending analysis
Type:
CWE-200
Information Leak / Disclosure
Publication date:
06/04/2017
Last modified:
20/04/2025
Description
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
Impact
Base Score 3.x
9.80
Severity 3.x
CRITICAL
Base Score 2.0
5.00
Severity 2.0
MEDIUM
Vulnerable products and versions
CPE | From | Up to |
---|---|---|
cpe:2.3:o:schneider-electric:modicon_tm221ce16r_firmware:1.3.3.3:*:*:*:*:*:*:* | ||
cpe:2.3:h:schneider-electric:modicon_tm221ce16r:-:*:*:*:*:*:*:* |
To consult the complete list of CPE names with products and versions, see this page
References to Advisories, Solutions, and Tools
- http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2017-097-02
- http://www.securityfocus.com/bid/97523
- https://os-s.net/advisories/OSS-2017-01.pdf
- http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2017-097-02
- http://www.securityfocus.com/bid/97523
- https://os-s.net/advisories/OSS-2017-01.pdf