CVE-2022-2502
Severity CVSS v4.0:
Pending analysis
Type:
CWE-20
Input Validation
Publication date:
26/07/2023
Last modified:
25/09/2024
Description
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Impact
Base Score 3.x
7.50
Severity 3.x
HIGH
Vulnerable products and versions
CPE | From | Up to |
---|---|---|
cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:* | ||
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1:*:*:*:*:*:*:* | ||
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2:*:*:*:*:*:*:* | ||
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3:*:*:*:*:*:*:* | ||
cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1:*:*:*:*:*:*:* |
To consult the complete list of CPE names with products and versions, see this page