CVE-2022-33174

Severity CVSS v4.0:
Pending analysis
Type:
Unavailable / Other
Publication date:
13/06/2022
Last modified:
27/06/2022

Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Vulnerable products and versions

CPE From Up to
cpe:2.3:o:powertekpdus:basic_pdu_firmware:*:*:*:*:*:*:*:* 3.30.30 (excluding)
cpe:2.3:h:powertekpdus:basic_pdu:-:*:*:*:*:*:*:*
cpe:2.3:o:powertekpdus:pm_pdu_firmware:*:*:*:*:*:*:*:* 3.30.30 (excluding)
cpe:2.3:h:powertekpdus:pm_pdu:-:*:*:*:*:*:*:*
cpe:2.3:o:powertekpdus:piml_pdu_firmware:*:*:*:*:*:*:*:* 3.30.30 (excluding)
cpe:2.3:h:powertekpdus:piml_pdu:-:*:*:*:*:*:*:*
cpe:2.3:o:powertekpdus:smart_pim_firmware:*:*:*:*:*:*:*:* 3.30.30 (excluding)
cpe:2.3:h:powertekpdus:smart_pim:-:*:*:*:*:*:*:*
cpe:2.3:o:powertekpdus:smart_pos_firmware:*:*:*:*:*:*:*:* 3.30.30 (excluding)
cpe:2.3:h:powertekpdus:smart_pos:-:*:*:*:*:*:*:*
cpe:2.3:o:powertekpdus:smart_pom_firmware:*:*:*:*:*:*:*:* 3.30.30 (excluding)
cpe:2.3:h:powertekpdus:smart_pom:-:*:*:*:*:*:*:*
cpe:2.3:o:powertekpdus:smart_poms_firmware:*:*:*:*:*:*:*:* 3.30.30 (excluding)
cpe:2.3:h:powertekpdus:smart_poms:-:*:*:*:*:*:*:*


References to Advisories, Solutions, and Tools