CVE-2022-4608
Severity CVSS v4.0:
Pending analysis
Type:
CWE-787
Out-of-bounds Write
Publication date:
26/07/2023
Last modified:
25/09/2024
Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Impact
Base Score 3.x
7.50
Severity 3.x
HIGH
Vulnerable products and versions
CPE | From | Up to |
---|---|---|
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1:*:*:*:*:*:*:* | ||
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2:*:*:*:*:*:*:* | ||
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3:*:*:*:*:*:*:* | ||
cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1:*:*:*:*:*:*:* | ||
cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:* |
To consult the complete list of CPE names with products and versions, see this page