Embedded malicious code vulnerability in Unitronics Vision1210

Posted date 06/07/2023
Importance
5 - Critical
Affected Resources

Vision1210, operating system version 4.3, build 5.

Description

INCIBE has coordinated the publication of a vulnerability affecting Unitronics' Vision1210 device, a PLC with integrated HMI, which has been discovered by Carlos Antonini Cepeda.

The following code has been assigned to this vulnerability:

CVE-2023-2003:

  • CVSS v3.1 base score: 9.1.
  • CVSS vector string: AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H.
  • Vulnerability type: CWE-506: Embedded Malicious Code. 
Solution

There is no reported solution at this time.

Detail

CVE-2023-2003: embedded malicious code vulnerability in Vision1210, which could allow a remote attacker to store base64-encoded malicious code in the device's data tables via the PCOM protocol, which can then be retrieved by a client and executed on the device.